Fluid Power Journal

Hydrostatic Transmission Components

HYDROSTATIC TRANSMISSION COMPONENTS today are of such high quality and efficiency they don’t allow enough exchange of oil in the loop to keep temperatures at an acceptable level. This is especially true if the transmission is heavily loaded during its work cycles. The oil simply goes from the pump to the motor or motors and back to the pump without getting a chance to return to the reservoir to cool and relax. Using a hot oil shuttle or loop-flushing valve can help remedy this situation.

One common mistake to look for when troubleshooting a circuit that has one of these flushing devices but still seems to be running over temperature is the improper setting of the shuttle valve relief cartridge.

When the transmission is in neutral, the connection to the low-pressure shuttle relief is blocked. The flushing valve at this point has no function, and charge pressure is controlled by the charge relief at the pump. When the transmission is operated either in forward or reverse, the low-pressure relief in the flushing block should now see the low side of the circuit, and if properly set, 30-45 psi (2-3 bar) below the charge pump relief will direct oil from the closed loop back to the heat exchanger and tank.

*Make sure to always verify the setting value of the shuttle relief. This will still provide sufficient design pressure to satisfy critical machine function needs such as brake release, two-speed shifting, etc.

Mark Perry, CFPHS, Fitzsimmons Hydraulics, Inc.

 

Share this information.

Related Posts

One thought on “Hydrostatic Transmission Components”

  1. robert scaggs says:

    one of the first things to check is to make sure the reservoir is not running low. The vast majority of equipment operators are not trained in hydraulic system operational requirements. They will continue to operate a system even if it is operating in an unacceptable condition, due to their lack of understanding of the damage this causes the system. A good indicator of chronic overheating is seal leakage. When rubber seals have been run at excessive temperatures for and extended period, they will become hardened. This prevents them from properly sealing. Remember that these seals need to be changed after the heating issue has been addressed because they will not “heal” themselves after they have been “cooked”.

Leave a Reply

Your email address will not be published. Required fields are marked *