By Robert Sheaf, CFPAI/AJPP, CFPE, CFPS, CFPECS, CFPMT, CFPMIP, CFPMMH, CFPMIH, CFPMM, CFC Industrial Training
A very simple power unit was having trouble reaching the needed 2,400 PSI relief setting. The unit was built with a fixed vane pump/motor unit where the pump was inside the reservoir and the electric motor mounted vertical on the reservoir top along with the directional valve and return filter. If they keep either solenoid energized with the cylinder bottomed out, the unit will only reach 1,800 PSI and the oil would start to overheat.
They screwed the relief setting to its maximum with no results. So, they decided to replace the pump. When it did not fix the problem, they were not sure if the cylinder was by passing or the valve was at fault, so they called in a service man from their local hydraulic shop.
What was the first thing he did when he started troubling the system?
When the service technician arrived, the first thing he did was “LOWER” the relief valve setting till there was little pressure when a solenoid was energized, and the cylinder bottomed out.
Then he increased the relief valve setting, and to the customer’s surprise, the system reached the required setting of 2,400 PSI. He advised them to always reduce the relief setting first as low as it could go so contamination that might be holding the relief poppet partially opened could pass into the reservoir. When I was doing a lot of troubleshooting, I would solve this problem several times a year by always “LOWERING” any pressure control first to see if had control of the system and if not return it to its original setting.
Robert Sheaf has more than 45 years troubleshooting, training, and consulting in the fluid power field. Email rjsheaf@cfc-solar.com or visit his website at www.cfcindustrialtraining.com. Visit fluidpowerjournal.com/figure-it-out to view previous problems.